MH Tech™ Conductor Ties are an engineered solution designed to secure overhead conductors onto pin insulators, ensuring mechanical stability, electrical integrity, and operational safety for 20 kV medium voltage distribution systems.
Manufactured from high-grade semi-conductive PVC engineered specifically for harsh tropical conditions, MH Tech™ ties deliver high mechanical tensile strength, outstanding resistance against intense ultraviolet (UV) radiation, humidity, and tropical heat, as well as self-extinguishing flame-retardant properties to prevent fire hazards from electrical arcing or lightning strikes.
Fully certified through independent laboratory testing by PT Qualis Indonesia in accordance with IEC, ASTM, and UL standards, MH Tech™ ties satisfy all primary technical criteria required for reliable electrical utility operations.
Efficiency for Straight-Line Pin Insulators
Applied to the top groove of pin insulators to firmly bind conductors along straight distribution lines. Provides robust mechanical holding while accommodating controlled micro-motion to dampen aeolian vibrations caused by ambient wind.
Flexibility for Angular Line Deviations
Engineered for pin insulators experiencing line angular deviations of up to ±15°. Specifically shaped to withstand lateral pull forces, holding conductors securely in the insulator's side neck groove.
Reinforced Grip for High Mechanical Stress
Designed for double crossarm arrangements or steep line deviations up to ±30° where tensile forces on the conductor are amplified. Employs a dual-grip loop mechanism to distribute stress evenly across two insulators.
Testing Laboratory: PT. Qualis Indonesia (Testing, Certification, Inspection, Calibration)
Report Number: QI-25/07/1419 | Test Period: July 24 – August 05, 2025 | Status: COMPLY / PASSED ALL CRITERIA
| No | Test Parameter | Method / Standard | Observed Results | Compliance |
|---|---|---|---|---|
| 1 | AC Voltage Withstand Test | IEC 61284 / IEC 62217 | 35 kV / 60 seconds | Passed (No Breakdown) |
| 2 | Partial Discharge Test | IEC 60270 | At 24 kV test voltage: • Top Ties: 48.84 pC • Side Ties: 49.24 pC • Double Side: 46.09 pC |
Passed (<50 pC) |
| 3 | Grip Strength (Tensile Holding) | IEC 61952 / ASTM D638 | • Top Ties: 1.29 kN • Side Ties: 0.89 kN • Double Side: 1.10 kN |
Passed (>0.4 kN) |
| 4 | Flammability Test | IEC 60695-11-10 / UL94 | Linear burning rate: 14.56 – 37.08 mm/min | UL94 HB40 Passed |
| 5 | Glow Wire Test | IEC 60695-2-11 | 850 °C tip temp, flame self-extinguished <30s, tissue paper unburned | Passed |
| 6 | Shore A Hardness | ASTM D2240 | Top: 87.2 HA | Side: 82.5 HA | Double: 85.0 HA | Passed (>79 HA) |
| 7 | Tensile Strength | ASTM D638 / IEC 60811 | 41.0 – 41.9 N/mm² (Required >40 N/mm²) | Passed |
| 8 | Elongation at Break | ASTM D638 / IEC 60811 | 49% – 58% (Required >10%) | Passed |
| 9 | Density | Customer Specification | 1.406 – 1.423 g/cm³ (Required >1.32 g/cm³) | Passed |
| 10 | UV Weathering Aging | ISO 4892-2 / IEC 62217 | 1000h Xenon Arc tropical exposure | No Cracks / Embrittlement |
Independent laboratory tests verify that MH Tech™ Conductor Ties are electrically safe (withstanding 35 kV test voltages with ultra-low partial discharge), mechanically superior (high holding load without slip), fire retardant (self-extinguishing and compliant with 850 °C glow wire criteria), and exceptionally durable under tropical weather. MH Tech™ represents a superior choice for advancing the reliability of medium voltage electrical grids.