MEDIUM & HIGH VOLTAGE CABLE JOINTING & TERMINATION
Cable Jointing and Termination represent critical high-precision engineering procedures required to connect separate cable lengths or transition insulated conductors to electrical apparatus terminals. When executed flawlessly, cable accessories restore the cable's electrical and mechanical integrity to the exact performance level of an uncut continuous conductor.
Stripping away copper metallic shielding and extruded semi-conductive screens produces an abrupt discontinuity in electrical field lines. This concentrated electric stress causes localized dielectric breakdown, partial discharge tracking, and eventual insulation flashover. Mitigating this electric stress requires precision dielectric stress-control elements engineered to smooth electrical gradient vectors along the insulation interface.
PT Mulya Jatra deploys certified jointers with extensive experience across Medium Voltage (MV 20 kV) and High Voltage (HV 70–150 kV) networks. Our installation workflows adhere strictly to PT PLN (Persero) standard operating procedures (SOP), utilizing certified calibrated testing equipment and authentic PRYSMIAN accessories.
Engineering Standards & Quality Objectives:
- Prevent localized electrical stress concentration at metallic shield cutoffs.
- Eliminate surface carbon track formation along external dielectric insulation under severe humidity and pollution.
- Provide hermetic environmental sealing against moisture ingress, UV radiation, and atmospheric pollutants.
- Ensure high-permittivity geometric stress relief across thermal expansion and contraction cycles.
Testing Specifications & Compliance Standards:
- IEC 62502-4 (2010-12): Full type-testing sequence including 54 kV AC / 48 kV DC withstand, partial discharge measurement at room temperature, impulse voltage testing, 30 thermal heating cycles in air at 30 kV AC, 30 submerged water-tank thermal cycles at 1-meter immersion, and dynamic short-circuit verification.
- IEEE 404: Standard for extruded and laminated dielectric shielded cable joints rated 2,500 V to 500,000 V.
- CENELEC HD 629-1: Accessory testing criteria for power cables with extruded insulation from 3.6/6 kV up to 20.8/36 kV.
Regular Client Portfolio:
- PT PLN (Persero) UID East Java, Jakarta Raya, Tangerang & Banten, West Java, and Bali
- PT Cikarang Listrindo Tbk
- PT GE Grid Solutions Indonesia
- PT CG Power Systems Indonesia